GC-1 Engine Generator Controller
 |
|
The GC-1 is designed to control and protect diesel engine driven generators. The controllers allow the generators to be synchronized and to share load. The GC-1 is designed with a standard Woodward digital controller that includes built-in diagnostics and protection functions. The GC-1 includes three phase current and voltage monitoring, a circuit breaker with solid state trip unit, breaker control switches, and kW/kVAR load sharing.
The engine is controlled via a speed trim signal that is sent to the engine controller that is supplied with the engine. The GC-1 can control Caterpillar, Detroit Diesel, Cummins, and other manufacturers. The generator excitation is controlled via a trim signal that is sent to the voltage regulator. This regulator is normally supplied with the generator but can also be supplied by Current Power Solutions in the control cabinet. The GC-1 can control synchronous generators supplied by Kato, Marathon, Caterpillar, GE, and most other manufacturers. |
 |
Ratings:
Generator Voltage |
480 or 600 Vac |
Generator Power |
Up to 3000HP |
Continuous Motor Current |
Up to 2700 Aac |
Frequency |
50 or 60 Hz |
Ambient Temperature |
0 - 50° Celsius (32 - 122° F) |
Cooling |
Water Cooling |
Dimensions |
87”H x 31.5”D
Width varies with Power |
Standard Features:
- Digital Controller
- Door Mounted Keypad
- Circuit Breaker with Solid State Trip Unit, Under-voltage Release, and Closing Coil
- Split-Core Current Transformers
- Potential Transformers
- 120V Control Power Transformer
- Manual Speed Adjustment
- Manual Voltage Adjustment
- Automatic Synchronizing
- Automatic Load Sharing
- Breaker Trip Switch
- 120V Generator Heater Supply
- kW, kVAR, Voltage, Current, and Frequency Metering on the Controller
- Generator Running Lamp
- Breaker Open & Breaker Closed Lamps
- Generator Fault Lamp
- Protection from Over-current, Reverse Power, Under/Over-voltage, Under/Over-frequency
Options:
- Manual Synchronization
- Differential current protection
- RTD monitoring
- Digital Voltage Regulator
- Switchboard Meters
|
|
 |